Methodology & Documentation
How Ardor calculates waste heat , which data sources we use, and which regulations our reports are based on. All technical terms are marked with a dashed underline — hover for definitions.
Heat Output Calculation Model v1.0
The calculation follows the thermodynamic principle that virtually all electrical energy in a data centre is converted to heat. The recoverable fraction depends on the cooling type.
Default Assumptions by Cooling Type
| Cooling Type | Temperature | ηcapture | Application |
|---|---|---|---|
| Liquid cooling (direct-to-chip) | 60–80°C | 70–90% | District heating, process heat |
| Hybrid cooling (air + liquid) | 40–60°C | 50–70% | Low-temperature district heating |
| Air cooling | 25–40°C | 30–50% | Greenhouses, building heating with heat pump |
Worked Example: 10 MW, Air Cooling, PUE 1.4
Annual energy = 14 MW × 8,760 h = 122,640 MWh/a
Recoverable = 122,640 × 0.50 = 61,320 MWh/a
≈ 3,066 German households (20 MWh/household)
Data Sources
Data Center Map
Public database of European data centres with addresses and operators.
OpenStreetMap
Industrial zones, commercial areas, facilities (hospitals, universities).
AGFW District Heating Map
Routing and coverage of German district heating networks. Energy efficiency association for heating.
Bitkom e.V.
Annual studies on PUE values and efficiency metrics of German data centres.
Uptime Institute
Global PUE averages and efficiency trends.
BAFA & BfEE
Official guidance on EnEfG reporting obligations and the waste heat platform.
Regulatory Foundations
§§ 11–13 EnEfG
Data centre-specific obligations: PUE targets, waste heat reuse quotas, annual filing to the Data Centre Register by 31 March.
§ 17 EnEfG
General waste heat reporting obligation. Enterprises consuming above 2.5 GWh final energy per year submit waste heat data to the BfEE platform by 31 March.
Regulatory Glossary
Key terms from the EnEfG, BAFA regulation, and waste heat utilisation in plain language.
Reports generated by Ardor are produced using automated methods. The operator is responsible for the accuracy of the data and for regulatory-compliant submission. Ardor assumes no liability for the use of reports vis-a-vis authorities. All methods, data sources, and assumptions are documented and verifiable in every report.